Benefits

  • Easy mounting

  • Maintenance free

  • "Fail Safe" function

  • Extensive self-control
    inclusive sensors

  • Simple and precise settings

  • Attractive design in anodized aluminium

    EC tested and DGP approved
Description:

FS 2000 is a speed control unit facilitating fail-safe
speed regulation of air ventilators
in ventilated burners - also burning gas.

FS 2000 is designed to overcome internal and
external errors - called fail-safe design -
any component failure will either result in a
safety-shutdown or the unit will continue operating
- still being safe.

FS 2000 reads out the measured speed of the ventilator
on a four digit LED display -
compares the speed to the demanded value
and performs a safety-shutdown of the burner if the
speed differs more than 1O % from the correct value.

Control loop for speed regulated motors. Enabling the fail-safe
use of frequency converters and other similar devices,
to control the speed of the air ventilator supplying
combustion air in gas and oil burners.                                

Forwarding a control signal modified by the internal electronic
calculated curve-band inside the unit. This way linking
corresponding fuel and air values - avoiding mecanical
solutions. Enabling close and safe operation -limiting excess
air to a small and reproducable value.

                               Application

Power supply:                 230 V AC 50/60 Hz
Power consumption:         Max. 10 VA
Prefuse:                          Supply           6 Amp
                                    
Contacts        6 Amp Quick blow
Dimensions:                   H x W x D 244x159x56 mm
Readout:                        1) Shaft RPM on a seven segment LED
                                     
2) Deviation from demanded curve.
Inputs:                           1) Proximitive sensor (Namur) on blower
                                         shaft one impulse per revolution
                                     
2) Potentiometer               1 Kohm ±3 %

Outputs:                         1) Contacts                      1 Making
                                                                          
1 Breaking
                                     
2) Current loop                4 - 20 mA
Lockout ranges:                ±10 % of demanded speed in the interval
                                     between 40 and 100 % of load signal.
                                     Linearly increasing to ± 15% in the
                                     interval between 40 and 0 % of load.
Lockout timing:                3 Sec. by decreasing speed
                                     
30 Sec. by increasing speed
Curve band:                     16 points between 0, 4, 8 , 12, 16, 21, 26,
                                     32, 38, 45, 52, 60, 68, 78, 89
                                     and 100 % of the load potentiometer.
                                     Used travel distance:
                                     
                                     4 to 96 % of potentiometer.

Settings:                        16 Potentiometers:

          
Point
Load signal
Range from Range to
 1
  
2
  
3
  
4
  
5
  
6
  
7
  
8
  
9
10
11
12
13
14
15
16
  0
   
4
   
8
  
12
  
16
  
21
  
26
  
32
  
36
  
45
  
52
  
60
  
68
  
78
  
89
100
 300
  
400
  
450
  
500
  
550
  
600
  
650
  
700
  
750
  
800
  
900
1000
1050
1100
1150
1200
 1400
 
1500
 
1600
 
1750
 
1900
 
2100
 
2250
 
2350
 
2500
 
2600
 
2700
 
2750
 
2800
 
2900
 
3000
 
3000

Back to Home

To download the complete leafletter
for this product

Click Here