Benefits:
    • No moving Parts

    • Automatic zeroing

    • Minimal maintenance

    • Robust, hermetically sealed
      stack units

    • Simple installation

    • Attractive design and compact design

    • Multiple outputs 4 - 20mA,
      RS 422/485 and contacts

    • Low price
Application:

The Model ODPM 2000 is based on the well proven
optical cross duct measuring principle comprising of
a stack mounted transmitter and receiver unit with
a remote µ-processor based monitor.

The instrument has been designed to project a
stabilised light source and cancel the effect of any ambient
light, with the result of providing an accurate and reliable
measure of smoke within the stack.
The monitor displays a reading of the percentage
opacity (Smoke Density) with a 4 to 20mA
and RS422/485 output.

The monitor also offers the facility to adjust the alarm level
with volt free alarm contacts and remote alarm or zero reset.

Efficient high volume blower units (optional)
maintain the optical lenses clean.



 

 Specifications (Monitor):

  • Display  4 pcs. 14 mm high
     seven segment L. E. D.'s
  • Outputs:  Analog Output: 4 - 20 mA max. loop
     resistance 500 ohm´s
  • Digital Output:  RS 422/485 interface.
  • Relay Output:  Potential free contacts carrying
     4 A at 240 Vac
  • Accuracy:  Better than ±1 % of scale
  • Ambient temperature:  0 - 50 oC
  • Supply Voltage:  240 (110, 220) Vac±10 % 50/60 Hz
  • Consumption:  10 VA
  • Alarm: Setting:  0 - 99 % of scale continuous set.
  • Delay: nbsp;5 seconds
  • Display:  Flashing
  • Resetting:  Relay released. Display flashing
     until value below
    set value.
  • Test:  100 % of scale simulated by
    &nbp;turning transmitter off.
  • Dimensions:  H x W x D:
     129mm x 61 mm x 215 mm + 25 mm
     outside panel
  • Fitting:  Single in a standard ABS-cabinet.
     
    Several in a standard 19" rack.

  • ABS-cabinet can be fitted in a panel cutout or on a
    wall. Rear part of cabinet removable for wire connection.

  • Temperature range: - 10 - 60 oC
     
     

Specifications (transmitter / receiver unit):

  • Fitting:  On a flange ending
     a 76mm (3")
     diameter extension tube
     with standard lengths of
     150, 300 or 450 mm.
  • Dimensions:  L x W x H:
     190 mm x 110 mm x 192 mm
  • Distance between
    transmitter and receiver:  0,3 - 6 Meter
  • Purge-air connections:  1" Tube Thread
  • Interconnection
    cable length:  Up to 100 meter between
     
    transmitter, receiver
     and monitor.
  • Temperature range:  - 10 - 60 oC.
 

To download the complete leafletter
for this product

Click Here